Installation / What is the acceptable moisture level for your adhesive?

What is the acceptable moisture level for your adhesive?

Parterre Universal Adhesive
Moisture testing must be performed utilizing both ASTM F1869 Calcium Chloride Test with moisture levels not to exceed 5 pounds per 24 hours per 1,000 square feet and ASTM F2170 in situ Relative Humidity (RH) Tests with RH not to exceed 95% in new construction and 90% in pre-existing buildings.

Parterre Lateral Adhesive
Moisture testing must be performed utilizing both ASTM F1869 Calcium Chloride Test with moisture levels not to exceed 5 pounds per 24 hours per 1,000 square feet and ASTM F2170 in situ Relative Humidity (RH) Tests with RH not to exceed 90%.

Parterre Adhesive #539P
Moisture testing must be performed utilizing both ASTM F1869 Calcium Chloride Test with moisture levels not to exceed 6 pounds per 24 hours per 1,000 square feet and ASTM F2170 in situ Relative Humidity (RH) Tests with RH not to exceed 75 percent.

Parterre Royal Epoxy Adhesive
Moisture testing must be performed utilizing both ASTM F1869 Calcium Chloride Test with moisture levels not to exceed 8 pounds per 24 hours per 1,000 square feet and ASTM F2170 in situ Relative Humidity (RH) Tests with RH not to exceed 85 percent.

Please refer to our Installation Guidelines specific to your product located in our Resource Center for complete information prior to your installation. For additional adhesive products to use in high moisture settings, contact us or your Parterre Sales Representative.